Valve Leakage Classifications
Types of Valve Leakage
There are two types of leakage from a valve,
namely; fugitive emissions from the valve to atmosphere, and leakage through
the valve but contained within the piping system.
Fugitive emissions can both be detrimental to the
environment and a potential safety hazard. Valves are considered to be the
major contributors to fugitive emission losses.
Leakage through the valve can also be a safety hazard, and can be detrimental to the process.
Reasons that Valves Leak
Common causes of valve leakage include:
- Valve is not fully closed. This can be due to
various reasons, including;
Standards for Acceptable Rates of Valve Leakage
There are many standards for classification of valve leakage rates e.g. DIN EN 917 covers Thermoplastics valves, BS 6364 covers cryogenic valves, however the three standards used most in the oil and gas, and petrochemical industry are API 598, ANSI FCI 70-2 and MSS-SP-61.
American Petroleum Institute (API)
The Americam Petroleum Institute standard API-598
covers the testing and inspection requirements for gate, globe, check, ball,
plug & butterfly valves. It has acceptable leakage rates for liquids as
well as gases. All valves built to the various API standards are required to
meet API-598 leakage criteria prior to shipment from the manufacturer or
supplier.
API598 states for shell and backseat tests, no
visible leakage is permitted. If the fluid is a liquid, there shall be no
visible evidence of drops or wetting of the external surfaces (no visible
leakage through the body, body liner, if any, and body-to-bonnet joint and no
structural damage). If the test fluid is air or gas, no leakage shall be
revealed by the established detection method. For both the low-pressure closure
test and the high-pressure closure test, visual evidence of leakage through the
disk, behind the seat rings, or past the shaft seals (of valves that have this
feature) is not permitted (Plastic deformation of resilient seats and seals is
not considered structural damage). The allowable rate for leakage of test fluid
past the seats, for the duration of the tests, is listed in the following
table:
Valve Size |
All Resilient Seated Valves |
All Metal-Seated Valves (except Check Valves) |
Metal-Seated |
||
Liquid Test |
Gas Test |
Liquid Test |
Gas Test |
||
<= 2" |
0 |
0 (b) |
0 (b) |
(c) |
(d) |
2.5" - 6"" |
0 |
12 |
24 |
(c) |
(d) |
8" - 12"" |
0 |
20 |
40 |
(c) |
(d) |
>= 14"" |
0 |
28 |
56 |
(c) |
(d) |
where
(a) 1 milliliter is considered equivalent to 16
drops
(b) There shall be no leakage for the minimum
specified test duration. For liquid test, 0 drop means no visible leakage per
minimum specified test duration. For gas test, 0 bubble means less then 1 bubble
per minimum specified test duration.
(c) The maximum permissible leakage rate shall be
0.18 cubic inch (3 cubic centimeters) per minute per inch of nominal pipe size.
(d) The maximum permissible leakage rates shall be
1.5 standard cubic feet (0.042 cubic meter) of gas per hour per inch of nominal
pipe size.
(e) For check valves larger than NPS 24, the
allowable leakage rate shall be per agreement between purchaser and
manufacturer.